5.5/10kW "Buck 3" Series Three-Phase PFC Rectifiers

  • Features
  • Applications
  • Characteristics
  • Specifications

    • Unique buck type step-down topology 

    • Typical Power Factor (PF): 0.99 

    • Typical efficiency: 97.5%  

    • Fully DSP control, smart and dynamic 

    • Baseplate conduction cooling 

    • EMC compliance with GJB151B-2013

    • Operation ambient temperature: -40~60℃ 

    • Operation baseplate temperature: -40~85℃ 

    • +24V isolated auxiliary power supply 

    • CAN bus interface

    • All round protections including output OVP,  output OCP and OTP

    • Military 

    • Industry


    Description

    Input voltage

    Output voltage

    Output Power

    Output Current

    Dimensions

    5.5kW 3-Phase Active PFC

    3-Phase AC 380V±15%

    DC 300~400V adjustable

    5.5kW

    13.75A

    280x192x38mm

    10kW 3-Phase Active PFC

    3-Phase AC 380V±15%

    DC 300~400V adjustable

    10kW

    25A

    329x231x39.5mm


    Parameter

    Notes and Conditions

    Min.

    Typ.

    Max.

    Units

    ABSOLUTE MAXIMUM RATINGS 






    Input Phase Voltage (RMS)

    Measured at Pins




    VAC

    Non-operation




    480

    VAC

    Operation




    456

    VAC

    Operation Temperature

    Baseplate Temperature

    -40


    85

    Storage Temperature


    -55


    105

    ISOLATION CHARACTERISTICS






    Isolation Voltage






    Input Pins to Output Pins

    Non-isolated

    0



    Vac

    Input Pins to Baseplate

    Enforced   Insulation

    3000



    Vac

    Output Pins to Baseplate

    Enforced   Insulation

    3000



    Vac

    Isolation Resistance


    100



    Mohm

    INPUT CHARACTERISTICS






    Operating Input Voltage Range   (RMS)

    Measured at Pins

    323

    380

    437

    VAC

    Input Undervoltage Protection(RMS)

    Measured at Pins

    312


    322

    VAC

    Input   Overvoltage Protection(RMS)

    Measured at Pins

    438


    448

    VAC

    Maximum Input Current (per phase)

    Measured at Po = 10kW @ 323VAC(rms)



    19.0

    A

    Power Factor

    Rated Input Voltage and Full Output Power

    0.98

    0.99



    Total Harmonic Distortion of AC Input Current

    Rated Input Voltage and Full Output Power


    2

    5

    %

    OUTPUT CHARACTERISTICS






    Output Voltage Range

    Vin= 380Vac

    300


    400

    V

    Output Voltage Regulation






    Line Regulation

    Io > 0.5A


    ± 1


    %

    Load Regulation

    Io > 0.5A


    ± 1


    %

    Temperature Coefficient



    0.2


    %/℃

    Output Ripple and Noise (peak-to-peak)

    Full Load, 20 MHz Bandwidth,  10uF 

    Tantalum Capacitor + 1uF Ceramic Capacitor



    8

    V

    Load Capacitance

    Full Load



    10,   000

    mF

    Output Current


    0


    25

    A

    Output Current Limiting

    Non-Latch Off

    25.5

    27.5

    29.5

    A

    Output Shutdown Voltage under Current Limiting

    Non-Latch Off



    100

    V

    Output Overvoltage Protection

    Non-Latch Off

    440

    445

    450

    V

    Efficiency

    Full Load

    97

    97.5


    %

    FUNCTION CHARATERISTICS






    Switching Frequency



    160


    kHz

    Weight



    4.5


    kg

    AUXILIARY POWER OUTPUT






    Output Voltage Range

    Enforced Isolated from Input and Output

    23

    24

    25

    V

    Source Current




    0.1

    A


RELATED    PRODUCTS