10/15kW “Boost 3” Series Three Phase PFC Rectifiers

  • Features
  • Applications
  • Characteristics
  • Specifications

    • Vienna-boost step-up topology

    • Typical Power Factor  (PF): 0.99 

    • Typical efficiency:  97.5% 

    • Fully DSP control, smart and dynamic 

    • Baseplate conduction cooling 

    • EMC compliance with GJB151B-2013 

    • Operation ambient temperature: -40~60℃

    • Operation baseplate temperature: -40~85℃

    • +24V isolated auxiliary power supply

    • CAN bus interface

    • All round protections including output OVP,  output OCP and OTP

    • Military 

    • Industry



    Description

    Input voltage

    Output voltage

    Output Power

    Output Current

    Dimensions

    15kW 3-Phase active PFC

    3-Phase AC 380V±15%

    DC   680~720V adjustable

    15kW

    22.5A

    376x218x44mm

    10kW 3-Phase active PFC

    3-Phase AC 380V±15%

    DC   680~720V adjustable

    10kW

    25A

    352.5x262x44mm


    Parameter

    Notes and Conditions

    Min.

    Typ.

    Max.

    Unit

    ABSOLUTE  MAXIMUM RATINGS 






    Input  Phase Voltage (RMS)

    Measured at Pins




    VAC

    Non-operation




    550

    VAC

    Operation




    495

    VAC

    Operation Temperature

    Baseplate Temperature

    -40


    85

    Storage Temperature


    -55


    105

    ISOLATION CHARACTERISTICS






    Isolation Voltage






    Input Pins to Output Pins

    Non-isolated

    0



    Vac

    Input Pins to Baseplate

    Enforced   Insulation

    3000



    Vac

    Output Pins to Baseplate

    Enforced   Insulation

    3000



    Vac

    Isolation Resistance


    10



    Mohm

    INPUT CHARACTERISTICS






    Operating Input Voltage Range   (RMS)

    Measured at Pins

    266

    380

    494

    VAC

    Input Undervoltage Protection(RMS)

    Measured at Pins

    255


    265

    VAC

    Input Overvoltage Protection(RMS)

    Measured at Pins

    495


    505

    VAC

    Maximum Input Current (per phase)

    Measured at Po = 10kW @ 323VAC(rms)



    33

    A

    Power Factor

    Rated Input Voltage and Full Output Power

    0.98

    0.99



    Total Harmonic Distortion of AC Input Current

    Rated   Input Voltage and Full Output Power


    3

    5

    %

    OUTPUT CHARACTERISTICS






    Output Voltage Range

    Vin = 380Vac

    680

    700

    720

    V

    Output Voltage Regulation






    Line Regulation

    Io > 0.5A


    ± 7


    V

    Load Regulation

    Io > 0.5A


    ± 7


    V

    Temperature Coefficient



    0.2


    %/℃

    Output Ripple and Noise (peak-to-peak)

    Full Load, 20 MHz Bandwidth, 10uF 

    Tantalum Capacitor + 1uF Ceramic Capacitor



    8

    V

    Load Capacitance

    Full Load



    2,   000

    mF

    Output Current


    0


    22.5

    A

    Output Current Limiting

    Non-Latch Off

    23

    25

    27

    A

    Output Shutdown Voltage under Current Limiting

    Non-Latch Off





    Output Overvoltage Protection

    Non-Latch Off

    770


    800

    V

    Efficiency

    Full Load

    97

    97.5


    %

    FUNCTION CHARATERISTICS






    Switching Frequency



    34


    kHz

    Weight



    5


    kg

    AUXILIARY POWER OUTPUT






    Output Voltage Range

    Enforced Isolated from Input and Output





    Source Current







RELATED    PRODUCTS